Technical data sheet
Universal interface 2 (4) IN, 2 (4) OUT
EK-CC2-TPEK-CD2-TP
Description
The Ekinex® universal interface is a KNX device that can be used as an input and/or output.
The device has: inputs for connecting conventional switches, push-buttons or sensors (not communicating natively on the KNX bus) or binary signals provided by other devices to the KNX bus to operate and control KNX bus functions; control outputs for driving low-consumption LEDs. The scanning voltage of the input channels is generated inside the device.
The device has an integrated KNX bus communication module and is designed for flush wall mounting or, with a support, on a 35 mm DIN rail. It is powered via the KNX bus and requires no auxiliary power supply.
Versions
EK-CC2-TP · 2 IN / 2 OUT
EK-CD2-TP · 4 IN / 4 OUT
Main features
- Technopolymer housing
- Programming push-button and LED on the case
- Connection to bus line with KNX terminal block
- Screw terminal blocks for connecting inputs and outputs
- IP20 protection degree (installed device)
- Weight 20 g
- Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
- Pollution degree 2 (according to IEC 60664-1)
- Dimensions (WxHxD): 43 × 43 × 16 mm
- Input terminals: max. cross-section 1 mm² (flexible), stripping approx. 5 mm, max. torque 0.2 Nm
- 30 Vdc power supply via KNX bus
- Current consumption from bus < 10 mA
Technical data
| Ambient conditions |
|---|
| Operating temperature | -5 ... +45 °C |
|---|
| Storage temperature | -25 ... +55 °C |
|---|
| Transport temperature | -25 ... +70 °C |
|---|
| Relative humidity | max 95% non-condensing |
|---|
Dimensions [mm]
Supply
The supply includes a terminal for connection to the bus.
Accessories
The following accessories are available to be ordered separately:
- Support for mounting on a standard 35 mm DIN-rail (code EK-SMG-35) and spring for snapping on the back of Ekinex® wall-mount devices (code EK-MAR-...) to be ordered separately.
Ordering information
| Code | Version | Packaging |
|---|
| EK-CC2-TP | 2 IN / 2 OUT | 1 pcs. |
| EK-CD2-TP | 4 IN / 4 OUT |
Configuration and commissioning
Via ETS5 or later versions
Application program: APEKCC2TP##.knxprod
(## = version, download from www.ekinex.com)
Documentation
For more information see the technical documentation, download from www.ekinex.com
CC2Scan the QR or open online CD2Scan the QR or open online