Technical data sheet
Universal I/O Module 8 outputs 8 inputs KNX ÆVO Series
EK-FG1-TP-I
Description
ÆVO built to last - Unbeatable reliability and resilience for a worry-free tomorrow.
The ÆVO Series universal I/O module EK-FG1-TP-I can control up to 8 groups of electrical loads, such as lights and valves, or up to 4 motorised drives, such as Venetian blinds and 3-way valves, independently and in any combination; for this purpose the device has outputs with potential-free bistable relay contacts that ensure the set control state is maintained even in the event of a power failure.
In addition, EK-FG1-TP-I allows the control of up to 8 drives, scenarios, up to 4 motors, dimmers, or the climate control of up to 8 rooms using the integrated thermostat/hygrostat function, by reading traditional commands and sensors equipped with potential-free contacts or passive NTC temperature probes; For this purpose, the device has 8 analog/digital inputs that can be configured independently with interrogation voltage produced inside the device.
The product is equipped with buttons for manual control and LEDs for status indication; a button allows switching between automatic and manual operation. The device has an integrated KNX bus communication module and is designed for mounting on a 35 mm profile rail. Power is supplied via the KNX bus and no auxiliary power supply is required.
Main features
- Technopolymer housing
- Buttons and LEDs for control and output status indication on the front panel
- Button and LED for programming or manual/automatic operation on the front panel
- Connection to bus line with KNX terminal block
- Connection of loads to the outputs via screw terminals for cables up to 4 mm²
- Connection of loads to the inputs via screw terminals for cables up to 0.5 mm²
- Connection of different phases on adjacent outputs
- 4 modular units (1 MU = 18 mm)
Technical data
|
|---|
| Voltage 30 Vdc via KNX bus |
| Bus supply voltage | 21-30 Vdc |
|---|
| Consumption from KNX bus | 10 mA standby, 54 mA at start-up |
|---|
|
|---|
| Number | 8 (bistable relays) |
|---|
| Voltage 250 Vac |
| Current | 16 A |
|---|
| Loads per output | LED lamps max 400 W, resistive 4000 W, inductive 1500 VA, capacitive 200 µF |
|---|
| Max. total current | 96 A |
|---|
|
|---|
| Number | 8 (configurable analogue/digital) |
|---|
| For passive temperature probes (NTC 10 kΩ at 25 °C) |
| For switches, buttons, or traditional potential-free sensors |
| Max. input cable length | 100 m (shielded cable above 1.5 m) |
|---|
|
|---|
| Operating temperature | -5 ... +45 °C |
|---|
| Storage temperature | -25 ... +55 °C |
|---|
| Transport temperature | -25 ... +70 °C |
|---|
| Relative humidity | max 95% non-condensing |
|---|
|
|---|
| IP20 protection degree (installed device) |
| Weight 277 g |
| Dimensions (WxHxD) | 71 × 90 × 63 mm |
|---|
Dimensions [mm]
Supply
The supply includes a terminal for connection to the KNX bus line. Any NTC temperature sensors to be connected to the inputs must be ordered separately.
Ordering information
| Code | Packaging |
|---|
| EK-FG1-TP-I | 1 pcs. |
Configuration and commissioning
Via ETS5 or later versions
Application program: APEKFG1TPI##.knxprod
(## = version, download from www.ekinex.com)
Documentation
For more information see the technical documentation, download from www.ekinex.com
Scan the QR or open online