Technical data sheet
Fan coil actuator/controller, 3-speed control
EK-HA1-TP
Description
The Ekinex® actuator/controller EK-HA1-TP allows a fan coil unit for room air conditioning to be operated. The device can act as a simple actuator in combination with a KNX room thermostat, or as a controller/actuator acquiring the temperature value from a KNX room probe or a probe connected to an analogue input.
The device is suitable for 2-pipe hydraulic distribution systems with ON/OFF control of an electrothermal drive for a shut-off valve and a fan with 3 speed levels. Outputs not used for controlling the fan coil unit can be configured as binary output channels to perform other functions. It also includes 2 inputs that can be freely configured as analogue or digital.
The device has an integrated KNX bus communication module and is designed for mounting on a 35 mm DIN rail. It is powered via the KNX bus; mains voltage 230 Vac is also required for operation.
Main features
- Technopolymer housing
- Front programming push-button and LED
- Connection to bus line with KNX terminal block
- Connection of inputs, outputs and 230 Vac power supply with screw terminals
- Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
- Overvoltage class III (according to EN 60664-1)
- Pollution degree 2 (according to IEC 60664-1)
- Installation on 35 mm rail (according to EN 60715)
- 4 modular units (1 MU = 18 mm)
- IP20 protection degree (installed device)
- Safety class II
- Weight 175 g
Technical data
|
|---|
| Voltage (load control) | 230 Vac 50/60 Hz |
|---|
| Voltage (electronics) | 30 Vdc via KNX bus |
|---|
| Current consumption from bus < 10 mA |
| Power from bus 300 mW |
|
|---|
| 2 freely configurable for passive temperature sensors (10 kΩ NTC at 25°C) or as potential-free binary inputs |
|
|---|
| 3 interlocked relay outputs to control a 3-speed fan (or configurable as binary outputs for different applications) |
| 1 relay SPST (single pole, single throw) to control an ON / OFF valve (in 2-pipe hydraulic distribution systems) |
| Fan output rating (V1, V2, V3) | 5(3) A, 250 Vac |
|---|
| DO1 output rating (valve or generic output): 5(3) A, 250 Vac |
|
|---|
| Operating temperature | 0 ... +55 °C |
|---|
| Storage temperature | -25 ... +55 °C |
|---|
| Transport temperature | -25 ... +70 °C |
|---|
| Relative humidity | max 95% non-condensing |
|---|
|
|---|
| Dimensions (WxHxD) | 72 × 90 × 60 mm |
|---|
Dimensions [mm]
Supply
The supply includes a terminal for connection to the bus.
Ordering information
| Code | Packaging |
|---|
| EK-HA1-TP | 1 pcs. |
Configuration and commissioning
Via ETS5 or later versions
Application program: APEKHA1TP##.knxprod
(## = version, download from www.ekinex.com)
Documentation
For more information see the technical documentation, download from www.ekinex.com
Scan the QR or open online