Technical data sheet
Three-phase secondary electricity meter for external KNX current transformers
EK-MS1-TP-TA
Description
The Ekinex KNX three-phase secondary electricity meter is a device for measuring active and reactive electrical energy with bidirectional metering of imported and exported energy, current, voltage, active and reactive power, power factor and other electrical parameters.
The 3 available measuring circuits are for connection via external current transformers (CT) and can also be used as independent single-phase circuits. The device has an integrated communication module for the KNX bus.
The meter provides electrical parameters on the KNX bus, has total/partial counters, comparators and other logic functions, and is configurable via ETS for integration into the energy management system with functions such as load control or threshold monitoring. The device is made for DIN-rail mounting according to EN 60715 inside switchboards and control cabinets.
Functions
- OLED display for displaying measured and diagnostic information
- Bidirectional measurement of electrical parameters for single-phase and three-phase circuits
- Connection of measuring circuits to current transformers via screw terminals for cables up to 4 mm²
- Accuracy better than 2%
- Connection to bus line with KNX terminal block
- Modular technopolymer housing 4 MU (1 MU = 18 mm)
Technical data
|
|---|
| Rated voltage Un | 3 × 230/400 V AC (+/- 20%) |
|---|
| Rated frequency fn | 50-60 Hz |
|---|
| Mains consumption | 12 mA @90 Vac, 6 mA @250 Vac |
|---|
| Current consumption from bus < 10 mA |
|
|---|
| Current transformers from Imax 5 A up to Imax 120 A (not included in delivery) |
| Measuring range with CT EK-MST | 5 A: 0,2-5 A; 20 A: 0,5-20 A; 60 A: 1-60 A; 120 A: 2-120 A |
|---|
| Measurement class PMD-II (CEI EN IEC 61557-12) |
|
|---|
| Operating temperature | -5 ... +45 °C |
|---|
| Storage temperature | -30 ... +70 °C |
|---|
| Max. rated casing temperature (tc): 80 °C |
| Relative humidity | 75% annual average, 95% short term, non-condensing |
|---|
| IP20 protection degree (installed device) |
|
|---|
| Weight | 300 g |
|---|
| Dimensions (WxHxD) | 71 × 90 × 62 mm |
|---|
Dimensions [mm]
Supply
The supply includes a terminal for connection to the KNX bus line. To be completed with EK-MST-…A current transformers, ordered separately.
Ordering information
| Code | Device | Qty |
|---|
| EK-MS1-TP-TA | Three-phase secondary electricity meter for external KNX current transformers | 1 |
Configuration and commissioning
Via ETS5 or later versions
Application program: APEKMSXTP##.knxprod
(## = version, download from www.ekinex.com)
Documentation
For more information see the technical documentation, download from www.ekinex.com
Scan the QR or open online