Technical data sheet
Current transformer for secondary electricity meter
EK-MST-5AEK-MST-20AEK-MST-60AEK-MST-120A
Description
Current transformer (CT) to be used with the KNX electricity meters with external transformer connection EK-MS1-TP-TA and EK-MS2-TP-TA.
Functions
- Technopolymer housing
- Ferrite core
- Connecting cable of approx. 1 m with free ends, not extendable
- Openable for easier installation
Main features
- No configuration required: the EK-MST-…A transformer version must be set in the application program of the EK-MSx-TP meter
Technical data
|
|---|
| Measuring range | 0,2-5 A (5A) · 0,5-20 A (20A) · 1,0-50 A (60A) · 2,0-120 A (120A) |
|---|
| Accuracy (active energy with 0.75 ≤ PF ≤ 1): < 2% |
| Transformation ratio | 1000:1 (5A, 20A), 3000:1 (60A, 120A) |
|---|
| Class 05 |
| Voltage level | 0,4/0,66/0,72kV |
|---|
| Withstand voltage level | 2kV/1mA/1min |
|---|
| Rated frequency | 50/60 Hz |
|---|
|
|---|
| Max. diameter of the through cable | Ø 10 mm (Ø 16 mm for EK-MST-120A) |
|---|
| Connecting cable of approx. 1 m with free ends, not extendable |
| Nylon housing, UL94-V0 classification |
| Black and white twin wire |
| Weight | 48 ... 93 g |
|---|
|
|---|
| For indoor use |
| Operating temperature | −40...+55 °C |
|---|
Dimensions [mm]
Versions
- EK-MST-5A: Primary 0-5 A / ratio 1000 at secondary (5 A-5mA)
- EK-MST-20A: Primary 0-20 A / ratio 1000 at secondary (20 A-20mA)
- EK-MST-60A: Primary 0-60 A / ratio 3000 at secondary (60 A-20mA)
- EK-MST-120A: Primary 0-120 A / ratio 3000 at secondary (120 A-40mA)
Ordering information
| Code | Device | Qty |
|---|
| EK-MST-5A | Current transformer for secondary electricity meter Primary 0-5 A / ratio 1000 at secondary (5 A-5mA) | 1 |
| EK-MST-20A | Current transformer for secondary electricity meter Primary 0-20 A / ratio 1000 at secondary (20 A-20mA) | 1 |
| EK-MST-60A | Current transformer for secondary electricity meter Primary 0-60 A / ratio 3000 at secondary (60 A-20mA) | 1 |
| EK-MST-120A | Current transformer for secondary electricity meter Primary 0-120 A / ratio 3000 at secondary (120 A-40mA) | 1 |
Documentation
For more information see the technical documentation, download from www.ekinex.com
Scan the QR or open online