Technical data sheet
8-channel actuator / controller for electrothermal valve drives
EK-HE1-TP
Description
The Ekinex® actuator/controller EK-HE1-TP allows valve drives in hydronic systems for room climate control to be operated. The device can act as a simple actuator in combination with one or more KNX room thermostats, or as a controller/actuator acquiring the temperature value from one or more KNX room probes.
The device is suitable for 2- or 4-pipe hydraulic distribution systems with ON/OFF control of electrothermal drives for shut-off valves.
The membrane keypad allows manual control and includes status LEDs; a button switches between automatic and manual operation.
The device has an integrated KNX bus communication module and is designed for mounting on a 35 mm DIN rail. It is powered via the KNX bus; mains voltage 230 Vac is also required for operation.
Main features
- Technopolymer housing
- Front programming push-button and LED
- Membrane keyboard with LEDs for status indication of outputs
- Push-button for switching operating mode (normal / programming)
- Connection to bus line with KNX terminal block
- Connection of outputs and 230 Vac power supply with screw terminals
- Screw terminals: max. cross-section 2.5 mm², stripping approx. 6 mm, max. torque 0.5 Nm
- Classification climatic 3K5 and mechanical 3M2 (according to EN 50491-2)
- Overvoltage class III (according to EN 60664-1)
- Pollution degree 2 (according to IEC 60664-1)
- Installation on 35 mm rail (according to EN 60715)
- 4 modular units (1 MU = 18 mm)
- IP20 protection degree (installed device)
- Safety class II
- Weight 160 g
Technical data
|
|---|
| Voltage (load control) | 230 Vac 50/60 Hz or 24 Vac |
|---|
| Voltage (electronics) | 30 Vdc via KNX bus |
|---|
| Current consumption from bus < 30 mA |
| Power from bus 720 mW |
|
|---|
| 8 TRIAC relays to control ON / OFF zone valve drives |
| 8 independent (2-pipe system) or 4 paired (4-pipe system) |
| Max. TRIAC output rating | 2(1) A |
|---|
| Max. 4 actuators in parallel per output (0.5 A (0.3 A) max) |
|
|---|
| Operating temperature | 0 ... +45 °C |
|---|
| Storage temperature | -25 ... +55 °C |
|---|
| Transport temperature | -25 ... +70 °C |
|---|
| Relative humidity | max 95% non-condensing |
|---|
|
|---|
| Dimensions (WxHxD) | 72 × 90 × 70 mm |
|---|
Dimensions [mm]
Supply
The supply includes a terminal for connection to the bus.
Ordering information
| Code | Packaging |
|---|
| EK-HE1-TP | 1 pcs. |
Configuration and commissioning
Via ETS5 or later versions
Application program: APEKHE1TP##.knxprod
(## = version, download from www.ekinex.com)
Documentation
For more information see the technical documentation, download from www.ekinex.com
Scan the QR or open online