M-Bus Master - KNX gateway

DIN-Rail mount modules

CODE: EK-BM1-TP-20

Description

The Ekinex® M-Bus - KNX Gateway performs a protocol conversion between an M-Bus and a KNX TP network. The device acts as M-Bus master. Versions for networks with a maximum number of 20, 40, 80 and 160 connected M-Bus slave devices are available. The device integrates a KNX bus communication module and it is suitable for mounting on a 35 mm DIN rail; it requires an auxiliary power supply.

Technical data
  • Power supply: from M-Bus network
  • Absorption at 24 Vdc: 3,5 VA (without load);
  • 4, 5, 8 or 14 VA (resp. with 20, 40, 80 or 160 M-Bus devices)
Communication
KNX side
  • KNX TP (Twisted Pair) communication port electrically isolated from power supply
  • Baud rate 9600 baud 
  • 1440-byte volatile support “KNX image” memory buffer
M-Bus side
  • M-Bus communication port (wired version, two-pole cable)
  • Selectable baud rate from 300 to 9600 baud 
  • Device addressing from 1 to 250
  • Variable reading through M-Bus slave device mapping
  • 1440-byte volatile support “M-Bus image” memory buffer
Configuration

Ethernet communication port (IEEE 802.3), RJ45 connector, minimum cable category: 5E

Delivery

The delivery includes the device and terminal blocks to connect to the KNX bus.

Other information

M-Bus (Meter-Bus) is a standard protocol for remote reading of data acquired from thermal energy, electricity, gas and water meters. M-Bus is fully compliant with EN 13757: Communication Systems for remote meter reading, parts 2 (Physical and connection layer) and 3 (Application layer).

Functions / Features
  • Plastic casing
  • Connection to bus line with KNX terminal block
  • Installation on 35 mm rail (according to EN 60715)
  • 4 modular units (1 MU = 18 mm)
  • IP20 protection degree (installed device)
  • Weight 145 g
Configurationa and commissioning

A detailed description of the parameters can be found in the application manual of the device. Configuration and commissioning require the application software CGEKBM1TPXX.exe (depending on the version XX = 20, 40, 80 or 160) (please contact the technical support)

This website or its third party tools use cookies, which are necessary to its functioning and required to achieve the purposes illustrated in the cookie policy. If you want to know more or withdraw your consent to all or some of the cookies, please refer to the cookie policy. By closing this banner, scrolling this page, clicking a link or continuing to browse otherwise, you agree to the use of cookies.